WHY NUMBERING LIKE 88,51 ARE USED IN ELECTRICAL CIRCUIT DIAGRAM?

SHARE

You might have seen Circuit diagram with symbols named with numbers and letter prefix and suffixes. Have you ever thought why it is named in such labels? If no please read this blog. We have described some of the widely used number labels and their meaning and functions.

Numbering is done as per ANSI/IEEE (American National Standard Institute/Institute of Electrical and Electronics Engineers) standard, these standards are widely used in labeling protection devices, relays, switches, etc.

Most commonly used numbering for power circuit are 88,42,6,51,52. For Example Star-Delta starter numbering is done as 88 for Main Contactor, 6 for Starting Contactor and 42 for Running contactor as shown in figure.

In some cases, you can find alphanumeric combinations like 63A. The number 63 stands for pressure switch and A stands for Air that means Pressure switch for Air. In control diagram X, Y and Z are reserved for Auxilary Relays. Find more details about available devices above and In end will discuss important one to remember so that your circuit tracing becomes easier without looking at starter panel.

DEVICES NUMBER & FUNCTION OF THE DEVICE

1MASTER ELEMENT is a device which gives an impulse locally or from a remote point, primarily to place an equipment into operation, out of operation, or both, either immediately or after a time delay.
2TIME DELAY STARTING OR CLOSING RELAY is a device which affords necessary time delay in placing an equipment into operation.
3Checking or Interlocking Relay. Normally these are Push Buttons or Control Switch.
4MASTER CONTACTOR OR RELAY is a device which makes and breaks the necessary control circuits:
A. To place the equipment in operation at the proper indication of the
master element and certain protective devices, and
B. To take the equipment out of operation at the opposite indication.
5STOPPING DEVICE is one which functions merely to place and hold an equipment out of operation.
6STARTING CIRCUIT BREAKER, CONTACTOR, OR SWITCH is a device
which connects machine to source of starting voltage. (The starting
breaker connecting the machine to starting voltage should always be No. 6. If a compensator is present the breaker energizing the compensator is No. 6C. If one breaker has a sufficient number of poles to perform both functions, it should be designated as No. 6. In Korndorffer starting (or continuous circuit starting), No. 6 is the Y breaker and No. 6C is the breaker on the high side of the compensator.)
7Rate of Change Relay
8CONTROL POWER SWITCH is a hand-operated switch which connects (or disconnects) the source of control power to control bus.
9REVERSING DEVICE.
10UNIT SEQUENCE SWITCH is a device which changes the sequence of
placing units in and out of service, in multiple unit equipments.
11CONTROL POWER TRANSFORMER is a transformer which supplies
the ac control power for operating the major ac devices.
12OVERSPEED DEVICE is a device which functions on machine overspeed.
13SYNCHRONOUS SPEED DEVICE is a device which indicates approximate or absolute synchronous speed.
14UNDERSPEED DEVICE is a device which functions on a decrease in
speed below synchronous or normal speed or failure of machine to
rotate.
15SPEED REGULATING DEVICE is a device for regulating the speed of a
rotating machine.
16BATTERY CHARGING CONTROL DEVICE is a device which controls
the dc automatically operated devices in a battery charging equipment.
17SERIES FIELD SHUNTING CIRCUIT BREAKER OR CONTACTOR is a
device which opens or closes a shunt circuit around a machine series field.
18ACCELERATING OR DECELERATING CONTACTOR, CIRCUIT
BREAKER, OR RELAY is one which causes the operation of a succeeding device in the starting sequence after the proper conditions have been established.
19STARTING-TO-RUNNING TRANSITION CONTACTOR OR RELAY is one
which gives an impulse to main circuit devices for changing a machine from the starting to the running connections.
20ELECTRICALLY OPERATED VALVE is a solenoid or motor operated
valve either in a vacuum, air, oil, or waterline. When several different types of electrically operated valves are furnished on one equipment, they will be designated as follows:
20 A Electrically operated valve for air
20 Q Electrically operated valve for oil
20 V Electrically operated valve for vacuum
20 W Electrically operated valve for water.
21IMPEDANCE RELAY.
22EQUALIZER CIRCUIT BREAKER OR CONTACTOR is a device which
makes equalizer connections for multiple unit equipments.
23TEMPERATURE REGULATING DEVICE is a thermal relay which
operates to hold temperature between given limits. Normally known as thermostat or temperature switch.
24BUS-TIE CIRCUIT BREAKER, CONTACTOR, OR SWITCH is a device
used to connect ac or dc buses together.
25SYNCHRONIZING OR PARELLELING DEVICE.
26APPARATUS THERMAL DEVICE is one which functions when given
value of heating of the apparatus to which it is applied has been reached.
27AC UNDERVOLTAGE RELAY is one which functions on a given value
of ac line or control voltage.
28RESISTOR THERMAL DEVICE is one which functions when a given
value of heating of the -load indicating, load shifting, or load limiting resistors have been reached.
29ISOLATING CIRCUIT BREAKER, CONTACTOR, OR SWITCH is a device
used for completely disconnecting one circuit from another, generally during emergency operation or test.
30ANNUNCIATOR RELAY is a nonautomatic -reset device which gives
individual visual indications upon the functioning of lockout protective devices, and may also be arranged to perform the lockout function in the master control circuit.
31SEPARATE EXCITATION DEVICE is one which connects a converter
shunt field to a source of separate excitation.
32DC REVERSE POWER RELAY is one which functions on a given value
of direct-current power reversal.
33POSITION SWITCH is one which indicates position of water wheel gate.
34MOTOR OPERATED SEQUENCE SWITCH is a motor-operated device
which fixes sequence of major devices during starting and stopping
sequence.
35BRUSH -OPERATING OR SLIP-RING SHORT CIRCUITING DEVICE is one for raising, lowering, or shifting the brushes of a machine, or for short circuiting the slip rings.
36POLARITY RELAY is one which indicates polarity.
37UNDERCURRENT OR UNDERPOWER RELAY is one which functions on a given minimum value of current or power flow.
38BEARING THERMAL DEVICE is one which functions upon excessive
bearing temperature.
39FIELD REDUCING CONTACTOR is one which inserts resistance in
field of machine.
40FIELD RELAY is one which indicates presence or loss of field in a
machine.
41FIELD CIRCUIT BREAKER, CONTACTOR, OR SWITCH is a device which functions to apply, remove, or reverse a machine field.
42RUNNING CIRCUIT BREAKER, CONTACTOR, OR SWITCH is a device
which connects a machine to source of running voltage.
43TRANSFER DEVICE is a device which transfers control of breakers,
etc., from automatic to test switches, or control of equipment from
manual to automatic, automatic to continuous, or performs some
transfer operation other than unit sequence.
44UNIT SEQUENCE STARTING CONTACTOR OR RELAY is one which
functions to start the next available unit, in multiple unit equipment on failure or overload of normally preceding unit.
45DC OVERVOLTAGE RELAY is one which functions on a given value of
dc machine or bus overvoltage.
46REVERSE-PHASE OR PHASE-BALANCE CURRENT RELAY OR POWER-
RECTIFIER MISFIRE RELAY is one which functions on an unbalanced current condition, or on reverse phase flow of current, or on misfire of power rectifier.
47SINGLE OR REVERSE -PHASE VOLTAGE RELAY is one which functions upon presence of correct polyphase voltage, or upon polyphase voltage of correct phase rotation, or both.
48INCOMPLETE SEQUENCE RELAY is one which gives indication to shut down a machine and prevent its restarting if the control does not properly complete a predetermined sequence.
49AC THERMAL RELAY is a thermal device which functions when the
temperature of a-c apparatus controlled tends to decrease below or
increase above the safe operating value.
50SHORT CIRCUIT SELECTIVE RELAY is one which functions on excessive rate of rise of current and may further allow reclosing only after normal conditions have been reestablished.
51AC OVERCURRENT RELAY is one which functions when current in an ac circuit exceeds a given value.
52AC CIRCUIT BREAKER OR CONTACTOR.
53EXCITER OR GENERATOR RELAY is one which indicates operating
values of exciter armature voltage or current or generator voltage, or insures positive building up of exciter or generator voltage, or indicates presence of generator field.
54HIGH-SPEED CIRCUIT BREAKER is a circuit breaker which starts to
open the main circuit in 0.01 second or less on excessive rate of rise
of current or on dc overload above its setting.
55POWER-FACTOR RELAY is one which holds or indicates a given power factor on an a-c machine or system.
56Field Application Relay
57Short-Circuiting or Grounding Device
58Rectification Failure Relay
59AC OVERVOLTAGE RELAY is one which functions on a given value
of ac overvoltage.
60VOLTAGE -BALANCE RELAY is one which indicates, or functions to
hold, a given voltage difference between two sources of voltage.
61CURRENT- BALANCE RELAY is one which indicates, or holds, a given
current relation between two sources of current.
62TIME -DELAY STOPPING OR OPENING RELAY is one which affords
the required time delay in the sequence of taking an equipment out of operation.
63FLUID-PRESSURE OR FLOW RELAY is one which indicates presence,
value or failure of oil, water, vacuum, or air pressure. May be used as a regulating or protective relay, or both. Also known as pressure switch. When several different types of pressure relays are furnished as one equipment, they will be designated as follows:
63A Pressure relay for air
63Q Pressure relay for oil
63V Pressure relay for vacuum
63W Pressure relay for water.
64GROUNDING PROTECTIVE RELAY is one which functions on failure of machine insulation to ground or flashover of dc machine to ground.
65GOVERNOR is the speed regulating device for a prime mover. Complete electrically operated governor parts are as follows:
65-A-Governor Accelerating Device (used during starting)
65-MF-Governor Fly Ball Motor
65 -ML -Governor Load Limit Motor
65 -MS -Governor Synchronizing Motor
65-S -Governor Solenoid.
66NOTCHING RELAY is one which functions to allow only a specified
number of operations of a given device, or equipment, or a specified
number of successive operations within a given time of each other.
Also is used to allow periodic energizing of a circuit.
67AC POWER-DIRECTIONAL OR AC POWER-DIRECTIONAL OVER-
CURRENT RELAY.
68DC THERMAL RELAY is a thermal device which functions when the
temperature of the dc apparatus controlled tends to exceed a safe
operating value. Also known as Blocking or Out-of-Step Relay
69PERMISSIVE CONTROL DEVICE.
70ELECTRICALLY OPERATED RHEOSTAT is one used primarily to
vary the resistance of a circuit in response to some contact making
device.
71DC LINE EMERGENCY CIRCUIT BREAKER OR CONTACTOR is one
used to interrupt a d-c power circuit under emergency conditions.
72DC LINE CIRCUIT BREAKER OR CONTACTOR is one used to close
and interrupt a dc power circuit under normal conditions or to interrupt this circuit under emergency conditions.
73LOAD RESISTOR CIRCUIT BREAKER OR CONTACTOR is one used to
insert a step of load limiting resistance in a power circuit under abnormal or overload conditions and to shunt this step of resistance when the abnormal or overload condition has disappeared.
73-1 for breaker or contactor shunting sequence if more than one
73-2 for breaker or contactor shunting in sequence
73-3 for breaker or contactor shunting sequence
73-4 for breaker or contactor shunting sequence.
74ALARM RELAY.
75POSITION CHANGING MECHANISM FOR REMOVABLE CIRCUIT
BREAKER UNIT.
76DC OVERCURRENT RELAY is one which functions on a dc overload
above a given amount. It may also be provided with specified dropout value so as to reclose load limiting resistor shunting circuit breaker or contactor, No. 73 for example, when the overload has disappeared.
76-1 functions with 73-1
76-2 functions with 73-2
76-3 functions with 73-3
76-4 functions with 73-4
77Telemetering Device
78Phase Angle Measuring Relay
79AC RECLOSING RELAY is a device which controls the reclosing of
an ac circuit interrupter.
80DC UNDERVOLTAGE RELAY is one which functions at a given value
of dc undervoltage.
81FREQUENCY DEVICE.
82DC RECLOSING RELAY is one which controls the reclosing of a dc
circuit interrupter.
83SELECTIVE CONTROL CONTACTOR OR RELAY is one which selects
between certain sources or conditions in an equipment.
84Operating Mechanism
85Communications, Carrier or Pilot-Wire Relay
86LOCKING-OUT RELAY is one which locks out equipment on abnormal conditions.
87DIFFERENTIAL CURRENT RELAY is one which functions on differential current of a given amount.
88AUXILIARY MOTOR OR MOTOR-GENERATOR is used for operating
equipment accessories such as pumps, blowers, etc. Also known as MAGNETIC CONTACTOR.
When auxiliary motors or motor generators are furnished on one
equipment for several different accessories, they should be designated as follows:
No. 88 B Auxiliary motor or motor generator for blower
No. 88 Q Auxiliary motor or motor generator for oil pump
No. 88 V Auxiliary motor or motor generator for vacuum
No. 88 W Auxiliary motor or motor generator for water.
89LINE SWITCH is one used as a disconnecting switch in a dc power
circuit.
90REGULATING DEVICE.
90C Current regulator
90P Power regulator
90PF Power factor regulator
90V Voltage regulator
90VAR Reactive power regulator.
91DC VOLTAGE DIRECTIONAL RELAY functions when the d-c voltage
exceeds a certain amount in a given direction.
92DC VOLTAGE AND CURRENT DIRECTIONAL RELAY is one used to
give indication to close a circuit when the voltage exceeds a certain
amount in a given direction, and to give the indication to open this
circuit when the current exceeds a certain amount in the reverse
direction.
93FIELD-CHANGING CONTACTOR OR RELAY is one which functions to
change the amount or source of excitation on a machine.
94TRIPPING OF TRIP-FREE RELAY OR CONTACTOR is one which
functions as a tripping contactor to trip out the equipment. (As a
trip-free relay, it functions to prevent immediate reclosure of a circuit interrupter, in case it opens immediately upon overload, even though the original closing circuit is still held closed.)
95, 97, 98, 99For specific applications where other numbers are not suitable
96Transmitter

Letters are used to define more specific function of the device. For example 63A Pressure switch for Air, Similarly when you have multiple devices of same number suffixes are added as 51-1, 51-2 , 51-n (n number to devices). Pleasse find list of prefixes and suffices used in numbering of device.

LIST OF PREFIXES & SUFFIXES

AAir, Automatic, Accelerating or Annuciater
BBattery, Bus, Blower, Breaking of Wire
CClose, Compensator, Closing Coil, Convertor, Common
CSManually operated control switch
DDirectional or Distance
EEmergency
FForward, Frequency, Float, Fan Feeder
GGround, Generator
HHigh, Hot, Holding, Heater, Horn
IInterlock
JInstant
LLamp, Low, Load, Limit, Line, Local
MMotor or Manual
NNormal
PPower
PFPower Factor
QOil or Quick
RReverse, Raise, Remote, Resistor, Reset
SSolenoid, Synchronizing or Switch
TTrip or Stop, Transformer, Timer
VVoltage, Vacuum
VARReactive power
WWater
XAuxilary Device
YAuxilary Device
ZAuxilary Device

Designing is done with these standard with proper numbering & adding suffices for more specific function. Most Basic similar kind of devices that you can find in Local Starter Panel or Group Starter Panel are

  • Contactors (88, 42, 6)
  • Breaker (52)
  • Overcurrent (51)
  • Push Button (3). Suffices may be added such as 3C for Closing, 3T for Stopping or Trip, 3R for Resetting, 3CF & 3CR for Forward and Reverse Operation of Motor direction.
  • Pressure Switch (63)
  • Temperature Switch (23)
  • Lamp (L). White Lamp(WL), Red Lamp(RL)
  • Auxilary Relay (X, Y, Z)
  • Timer (T)

CONCLUSION

This information you can find in the maker manual its similar to ANSI/IEEE standard and they design with the same. Maker manual has added a correct suffix to describe specific function of the device. It saves time in reading circuit diagram and easier for tracing only when you remember ANSI/IEEE standard of numbering devices. Apart from this practice circuit symbols.

GOOD LUCK